These Fire Alarm Experts Get a Failing Grade
When Installing a FM 200 System In a School for at Risk Children
By Nick Markowitz
Jr.
Fire Investigator
One of my many institutional clients, which runs
a day school program for At risk youth and Adjudicated Youth who are staying
on the campus in the residence program, called me the other day and wondered
if I could temporarily disarm the FM 200 Clean Agent system they have in their
computer room. They forgot about air conditioning men working with torches, which
might set it off and the company who installed it could not get someone on site
for several hours.
I take care of all the alarms on the campus and the computer department never
let me know this system had been installed in this school. I arrived and temporarily
took the system off line and then started asking questions when I failed to get
a trouble signal on the main school fire panel that I should have. Well as usual
it turns out codes were once again not followed by the company who goes around
telling everyone they're fire alarm experts.
First off the FM 200 system panel is required by code to be tied to the main
fire system, as would a kitchen hood in a school cafeteria, the sprinklers etc.
They also never got permits from the AHJ nor did they file the sealed plans drawn
by a professional as required by the UCC that was in effect when they installed
the system. They also failed to install automatically closing doors to insure
the clean agent stays in the room and puts out the fire. They also failed to
tie into the ac unit in the ceiling so it stops operating when the system activates.
Add all this to the fact immediately outside the computer room is classrooms
for 100 grade school students who would have no idea the FM 200 system has activated
and could be filling up their classrooms with Halitron (Freon) Gas, if the doors
fail to seal off the gas.
Again nothing but excuses from this company who claim they did only what they
had to do and that the system is perfectly safe and installed properly. Unfortunately
there ineptness for now the 3rd time on campus has been the straw that broke
the camels back and they will be doing no further work at this campus. What further
angered the AHJ was the fact besides not notifying him about the install they
never notified the local fire dept of the fact they could be walking in on a
FM 200 system that has dumped 100 pounds of Halitron and could be dangerous if
the gas becomes heated as Freon produces Phosgene gas known during WWI as nerve
gas. Everytime I have installed a Fire System I have always let the AHJ know
what is going on and invited the local fire dept through for a company inspection
so they know how to respond and reset it. Its just good practice to do so. Something
this company does not care to do. Despite the fact many of there techs are in
fact volunteer firefighters. But this is not the first time I have run into problems
with these clean agent systems.
I have a customer who bought an old machine shop building which in its Engineering
Dept. had an older style Halon system installed in its computer room, with one
big problem. When the pull station was installed to activate the Halon Trip it
was installed directly next to a light switch and one day an employee poking
around in the darkened room found the wrong switch and tripped the system. My
customer heard the alarm go off ran back and got his employee out to a safe area
till the gas dissipated. When I checked out the pull station I found it was one
that had been recalled for causing false activations and when the company that
did the install wrongly was asked to move the pull station and reset the system
and fill the tank, they refused until the AHJ who again was never notified the
system was in the building started procedures against them. This once again proves
that Fire system installing companies think they can get away with any kind of
install they want and do not need to meet the minimum requirements of the code.
If a contractor can not meet the minimum building code requirements of the UCC
which are very minimum at that in many cases, then they have no business doing
any work in this or any state.